The Glitch
Overview: A manually set three-way mixing valve was installed to
regulate the supply temperature to the concrete-slab radiant floor system. A
bypass valve is also installed to help boost the boiler inlet temperature.
Exercise: Assume the system undergoes a few modest nighttime setback
periods as it operates through the heating season. What are the problems with
this design?
The Fix
One of the problems with
the design is the boiler is still not “guaranteed” to be protected against flue
gas condensation. A high-mass slab can easily absorb heat from the water faster
than the boiler can reproduce that heat by burning fuel. When this happens,
neither the manually set 3-way valve nor the bypass will prevent the boiler
temperature from dropping ― quite possibly well below the dew point of the flue
gases. This is especially likely during recovery from setback periods.
To correct this situation, the
3-way valve needs to have some “smarts.” Equipping it with an
actuator/controller that monitors boiler inlet temperature allows the 3-way
valve to operate as a thermal clutch when necessary to prevent flue gas
condensation. This is shown a fix No. 1.
Assuming the boiler has low
flow resistance and significant thermal mass (both typical of cast-iron
sectional boilers), the boiler circulator can be very small and thus operate at
low wattage.
A set of closely spaced tees ensures that the flow dynamics
of the distribution system are hydraulically separated from those of the boiler
loop.
An even better solution is to use a 4-way motorized mixing valve
with the same sensors and eliminate the need for the boiler circulator (shown
as fix No. 2). Just be sure to keep the valve close to the boiler and minimize
the head loss in the piping connecting the boiler to the valve. Why use an
extra circulator when you don’t need to …
By: Chris H
Posted: April 5, 2008 7:57 PM