The Glitch
Overview: The system below uses a gas-fired cast-iron boiler
to supply three zones of low-temperature floor heating. The installer selects a
1-inch-pipe-sized three-way thermostatic mixing with Cv=3.5 for the mixing
device. Each zone is piped in parallel from a common header downstream of the
mixing valve.
Exercise:
Find at least five errors in this layout.
The Fix
There
are several problems with the original schematic. They are corrected in the
schematic shown.
First, the zone circuits are not equipped
with check valves. Without them, reverse flow will develop in circuits that are
off. The fix is to either install check valves or use circulators with integral
flow checks as shown.
Another serious error is the flow
capacity of the three-way thermostatic mixing valve. A valve with a Cv of 3.5
means that a 1 psi pressure drop will occur with a 3.5 gpm flow rate. If we
assume a conservative 20-degree temperature drop on the manifold stations, the
required design load flow rate would be 12 gpm. At this flow rate, the pressure
drop through the thermostatic valve would be almost 12 psi! This is way beyond the
capacity of typical 1/25 horsepower zone circulators and, thus, it simply won’t
occur.
Instead, flow through the zone circuits will be
severely restricted and heat delivery would suffer the same fate. The fix is to
use a mixing valve with a higher Cv rating. Select a valve with a Cv
approximately equal to the full design load flow rate; this will limit pressure
drop through the valve to about 1 psi under these conditions.
Still another problem on the original schematic is a lack
of boiler inlet temperature protection. There is no provision for a mixing
point to boost boiler inlet temperature. Furthermore, there is nothing to
“react” to lower boiler inlet temperature; thus, the boiler is not protected
against flue gas condensation.
The fix is to use a motorized
three-way valve with a controller that measures boiler inlet temperature and,
when necessary, restricts the flow of hot water into the valve so that flue gas
condensation does not occur within the boiler. The circulator in the boiler
loop is necessary to create the second mixing point that boosts boiler inlet
temperature.
Other errors are:
- Circuit purging valves installed backwards.
- Zone circulator inlet too close to header (allow minimum
12 pipe diameters of straight pipe on inlet to any circulator).
By: John P. Callan
Posted: January 13, 2010 8:27 PM
By: Kelly Faloon
Posted: January 19, 2010 1:03 PM
By: Curtis
Posted: January 27, 2010 10:57 AM
By: Eric Svensson
Posted: January 29, 2010 12:35 PM
Eric.svensson@trane.com
By: Dave
Posted: February 24, 2010 10:49 AM
By: siggy
Posted: February 24, 2010 2:10 PM
siggy
By: Ivan
Posted: March 8, 2010 10:03 PM
By: Darren
Posted: March 25, 2010 12:29 PM