Peculiar Piping
by John Siegenthaler, P.E.
May 20, 2009

ARTICLE TOOLS
EmailEmailPrintPrintReprintsReprintsshareShare



The Glitch

Overview: An installer plans to use a low mass boiler with several heating zones and an indirect water heater. Fearing burner short cycling, he adds a buffer tank, and pipes it all together as shown below.

Exercise: Can you spot at least five details that are incorrect?


The Fix

To say this system is a piping aberration is going easy on it.

1. The indirect water heater should not interact with the buffer tank when it needs heat. The indirect tank has sufficient thermal mass of its own to prevent boiler short cycling. Even if the zone valve leading to the indirect opens when the tank aquastat calls for heat there would be very little flow through the tank. Most of the flow created by the buffer tank circulator would just do a U-turn at the closely spaced tees and head back into the buffer tank.

2. When it operates, the boiler circulator would create differential pressure between the headers at the top of the schematic. Although the zone valves would likely not bleed hot water to their zones when closed, it is very likely there will be unexpected flow into the two zones using circulators. The forward opening resistance of their check valves would not be able to hold back the differential pressure created by the boiler circulator.

3. The boiler circulator is pumping toward the expansion tank connection point. It should be pumping away from this point.

4. The circulators are shown with their inlet very close to the supply header. There should be at least 12 pipe diameters of straight pipe leading into the circulators.

5. There is no differential pressure bypass valve shown on the headers serving the zone valves.

6. The left-most zone circuit will not be able to draw heated water from the buffer tank.

7. Although the heat exchanger of the indirect tank has its inlet at the top and outlet at the bottom, the temperature gradient inside the tank is inverted. This would imply upside down temperature stratification, and nature is not going to allow that. (Just seeing if you’re paying attention.)

The fix drawing shows all corrections to the above problems.

The indirect water heater is piped as a separate circuit, and would likely operate with priority control.

Upon a call for space heating, the system’s controls check to see if the buffer tank is sufficiently warm to serve as the heat source. If so, the boiler is not fired, the boiler circulator remains off, and the buffer tank circulator operates. When the buffer tank has cooled through its differential, the boiler fires and the boiler circulator operates. The buffer tank circulator remains on. Heated water is supplied to the active zone(s), and any access heat is routed to the buffer tank, causing its temperature to rise. If the buffer tank climbs back up to its upper temperature setting the boiler and boiler circulator are turned off, and the above sequence repeats itself.

A spring-load check valve at the top outlet of the buffer tank helps prevent heat migration.


John Siegenthaler, P.E.
john@hydronicpros.com
John Siegenthaler, P.E., is principal of Appropriate Designs, a consulting engineering firm in Holland Patent, N.Y., and author of the text “Modern Hydronic Heating.” Visit www.hydronicpros.com for information on new software for hydronic system design and documentation. John is also the contributing editor to PM's monthly "The Glitch & The Fix" column, which offers hydronic troubleshooting solutions in conjuction with the magazine's twice-monthly Radiant & Hydronics eNews newsletter. You can reach John by e-mail at john@hydronicpros.com.

Links

  Comments (2)Post a Comment
Title: May 2009 Glitch & Fix


#1 The PDF Format link (232 kb) does not work

#2 I knew that this Glitch was identical or similar to a previous one.

Nov. 2007 is a close cousin

Keep up this interesting series


Title: PDF now working


Sorry for any inconvenience ... The PDF is now working properly.


 

No HTML or BBCode in comments please.
 


PMmag.com

Visit Plumbing & Mechanical website.


PMEngineer.com

Visit PM Engineer website.


SupplyHT.com

Visit Supply House Times website.


ReevesJournal.com

Visit Reeves Journal website.


Bath and Kitchen Pro

Visit Bath & Kitchen Pro website.


RadiantandHydronics.com

Visit Radiant & Hydronics website.


Radiant + Hydronics eNews
Click the button below to sign up for the Radiant + Hydronics eNews.


Bath & Kitchen Pro eNews
Click the button below to sign up for the Bath & Kitchen Pro eNews.


PVF E-News
Click the button below to sign up for the PVF E-News.


PME E-News
Click the button below to sign up for one of PME's free E-Newsletters.














Water Quality Association
Want to know more about water? Then look no further than WQA's Water Information Library - a new cross-industry database of information consisting of articles from the top industry publications as well as WQA's own extensive technical papers and resources.


College of Product Knowledge CD by Don ArnoldCollege of Product Knowledge CD by Don Arnold

Invest in the best-read series ever published for the Plumbing Industry & the most highly acclaimed product training CD. Knowledge is an investment
Click Here




home   |    latest news   |     calendar   |    blog   |    buyers guides   |    media kits   |     RJ's Tool Bin   |     store   |    contact   |    links