The Fix
|
|
| What happens when both circulators operate
|
|
This one took some head scratching. What we eventually found was
that the pressure differential created by the high head circulator supplying
the radiant portion of the system ― in combination with the high flow
resistance through the compact tankless coil ― was creating a situation where
the pressure in the return header was several psi higher than that in the
supply header. This pressure differential was present whenever the high head
circulator operated. It was also greater than the “shut off” differential
pressure of the smaller circulator (e.g. the maximum pressure differential the
small circulator can create). This backseated the check valve in the indirect
circuit, and “deadheaded” the small circulator.
Pressures representing the situation with both circulators running are shown in
the first fix drawing. Notice that the pressure on the discharge side of the
small circulator is 10 psi. This is 5 psi higher than at its inlet, and it’s
the maximum pressure differential it can muster. At the same time the high flow
resistance of the tankless coil causes the pressure in the return header to be
12 psi. Hence the lower flow check is backseated and there is no flow through
the heat exchanger in the water heater.
We corrected the situation by rewiring the indirect water heater
to operate as a priority load (i.e., the easier fix). However, using a
hydraulic separator as shown in the fix drawing could have eliminated this
interference. A separate circulator would provide flow through the boiler. The
pressure differential created by this circulator would be isolated from the two
distribution circulators. The latter would also be isolated from each other by
the hydraulic separator in combination with the “short and fat” headers.
The moral of the story: When big circulators and small circulators
can “see” each other (e.g., each can sense the pressure differential created by
the other) they will “fight”. If the heat source and common piping produce high
flow resistance, the fight will be intense, and the big circulator will win
every time. Stop the fights – provide hydraulic separation of circuits.
Other changes in the fix drawing include:
- Adding purging valves on the return side of
each load circuit
- Moving the expansion tank connection point
near the bottom of the hydraulic separator
- Eliminate the original “bullhead tees” between
the flow checks
- Putting the flow check valves on the supply
side of each load circuit to help minimize heat migration