The Fix
Let’s start
with the heat source: The cardinal rule of multiple boiler systems is to only
provide flow through a boiler that’s operating (and perhaps for a short
post-purge period at the end of a firing cycle).
There is no
way the original system can do this.
The solution is to install a separate circulator and flow check on each boiler,
and wire them to operate only when their associated boiler is providing heat to
the system. In The Fix drawing, I’ve shown circulators with integral check
valves mounted with the check valve under the circulator. This reduces the
possibility of air being trapped in the circulator by the check valve. Ball
valves are also provided to allow each boiler to be isolated if necessary.
Another error
is the use of high head circulators with zone valves. This is never a good
idea. It produces wide variations in differential pressure depending on which
zones are operating. If a fixed speed circulator will be used with zone valves,
it should have a flat pump curve. A differential pressure bypass valve should
also be installed across the headers to help minimize variations in
differential pressure.
Zone valves
should be located on the supply side of the zone circuits to help prevent heat
migration into inactive zone circuits.
Purging
valves should be provided on all circuits.
The original
distribution system is an “aberration” ― a mix between a pumped boiler loop,
and parallel circuits piped “across the mains.” The partially closed ball valve
at the end of this loop will create a differential pressure across the mains
that will drive hot water through inactive zone circuits.
There is
absolutely no reason to use such a valve. The situation is corrected by a
simple pair of closely spaced tees in combination with generously sized
headers. This provided effective hydraulic separation between all the
circulators, and eliminates the need for a primary circulator.
Finally, the
two zone circuits on the right side of the original system do not have flow
check valves or purging valves.